Section 2 - TELECOMMUNICATIONS ROOMS AND CABLE TERMINATION
2.1 OVERVIEW
- 2.1.1 DEFINITION
Telecommunication rooms are
special-purpose rooms that house telecommunications equipment and
wiring. These rooms have specific requirements due to the nature,
size and complexity of the equipment and wiring housed in the
room.
- 2.1.2 SPACE
There are two different types of
telecommunications rooms within a building, each supporting
critical functions as part of the building wiring and
communications systems. In general, each room must be large enough
to accommodate the wiring and equipment, which will be located
within them, plus additional space for growth. The two types of
rooms are:
- The Telecommunications Distribution Equipment Room (TDER),
Main Distribution Frame (MDF) or Main Cross-connect (MC). MC
will be used here. There is normally only one MC per building.
This room may serve as what is sometimes called the node room
and house Data Switches, Routers, and Telecom related electronic
equipment.
- The Wiring Closet, Intermediate Distribution Frame (IDF),
Intermediate Cross-connect (IC), Horizontal Cross-connect or
Telecommunications Room (TR). TC will be used here. There is
at least one TC per floor. More than one TC per floor is
required when the terminated wiring distance between any
communications jack and the TC exceeds 295 feet (90 meters).
The preferable minimum size for a Telecommunication Room is 100
square feet and the preferable dimensions for this room are 10'X10'.
In no case shall this room be less than 100 square feet, with the minimum
dimension of any side being 8 feet. This room may be shared with telephone
equipment, data network equipment and racks. Telecommunications Center shall
be contacted for final dimension approval.
- 2.1.3 GENERAL
Project specifications will
indicate that Telecommunications Center personnel or its designee
are responsible for furnishing, installing and terminating the
various types of communications cabling, racks, panels and other
items specified in Section 2.
All work shall comply
with the National Electrical Code, Local Building Codes, and the
University of Mississippi Facilities Management standards.
NOTE: Telecommunications rooms may vary according to
the size of the building, number of floors, tenancy
characteristics and telecommunications services required.
Consideration to the future needs of the facility and the end
users is a necessity. Telecommunications Center will have final
approval on room dimensions.
Electrical panels, other
than those exclusively servicing the telecommunication room in
which it is located, are strictly prohibited in telecommunications
rooms. Services which are not telecommunication related, shall
also be prohibited in these rooms. This includes, but is not
limited to, janitorial services, supply storage, departmental
storage, etc. There shall never be an exception to these
restrictions. Fire alarm and security panels are not permitted in
telecommunication rooms.
A 50 percent growth factor
shall be built in and provided in each riser unless otherwise
specified; consequently, any cable or conduit work that pertains to
telecommunications must be designed and/or approved by
Telecommunications Center. Project specifications will include
this growth factor.
To facilitate the proper
installation, routing and placement of cables, wires, premise
equipment and terminal fields, telecommunication closets shall be
located on each floor, as close as possible to the middle of the
building and stacked one above the other, unless otherwise
instructed or approved by Telecommunications Center. Architects
and Engineers must pay special attention to telecommunication
closet locations to overcome distance limitations. The total
distance of the conduit path, from outlet to the TC or MC, when
the MC also serves as a TC, shall not exceed 295 feet (90 meters)
including termination loss.
Every PC or other single
device with a network connection must be cabled back to the
nearest telecommunications closet in the building. The
telecommunication room(s) shall house all and only the equipment
directly related to the telecommunications systems and its
environmental support systems.
"As Built" drawings
shall be submitted by the project contractor to Telecommunications
Center with each job upon acceptance. These drawings will be used
by Telecommunications Center and various other University of
Mississippi departments.
2.2 REQUIREMENTS
- 2.2.1 GENERAL
All telecommunications room
doors are to be keyed alike and according to the Facilities Management
specifications.
Doorways shall be designed with minimum
measurements of 3'-0" by 6'-8" and shall open outward into the
corridor.
Floors shall be sealed concrete or tile,
carpet is prohibited.
Telecommunication rooms shall be
located above any threat of flooding. Rooms located in basements
shall have floor drains with positive drainage, otherwise sump
pumps must be provided. When sump pumps are required, they shall
be connected to an emergency power supply.
Fire rated
plywood, 3/4 inch thick, must be mechanically fastened to the
walls specified in the project specifications of each Main
Cross-connect Room and Telecommunication Closet. The fire rated
plywood must be fastened in a way that is easily removable. The
fire rated plywood shall be painted with two (2) coats of fire
resistant paint of a neutral color. The fire rated plywood is to
begin at four (4) inches AFF (above finished floor) and end at
8'-4" AFF.
The recommended ceiling height is minimum
8'-6". Finished ceilings are not required in telecommunications
rooms.
Install a minimum of 4 (four) 4 inch sleeves
between telecommunications rooms, with sleeves extended 4 (four)
inches AFF. In buildings with Plenum rated ceilings, EMT
multi-cell conduit shall be used to connect telecommunication
closets together. Buildings taller than 4 stories shall require an
increase in the minimum number of sleeves as follows:
- 5-8 stories: 8 sleeves floors 1-4 / 4 sleeves floors 5-8
- 9-12 stories: 12 sleeves floors 1-4 / 8 sleeves floors 5-8 /
4 sleeves floors 9-12
- 2.2.2 ENVIRONMENT
All telecommunications
rooms shall be environmentally controlled to maintain the room
environment at a temperature range of 65 to 75 degrees Fahrenheit,
with a relative humidity level of 35 to 75 percent non-conducting,
24 hours a day, 7 days a week. Telecommunications rooms shall be
conditioned with a fresh air exchange of three (3) air changes per
hour. If HVAC must be shut down then an exhaust connected to
emergency power must be provided to remove heat. Generally the
system must remove 7,000 BTU per hour.
No plumbing,
HVAC, or electrical conduit shall pass through or be directly
above any telecommunications room.
- 2.2.3 ELECTRICAL
Lighting shall be four (4)
foot fluorescent type and provide a minimum of 50 FC at 3 feet
above the floor and be connected to the emergency generator when
available.
A minimum of two 240V and four double duplex AC outlets
must be provided to power telephone system components, computer
interfaces, network electronics and other telecommunications
requirements. Outlets must be flush when cut through plywood.
Outlet locations will be determined during the building design
stage.
Each double duplex outlet shall be connected to
a dedicated circuit breaker. Each dedicated electrical circuit
shall be 20-amp, 120V, 60 HZ type. All circuits must be tied to an
emergency generator when available. All outlets shall be labeled
with panel and circuit location.
All breaker panels are to be labeled and identified to avoid being
turned off in error. Breakers servicing the telecommunication room shall
be equipped with locking devices to prevent turn off.
- 2.2.4 GROUNDING
All telecommunications rooms
shall have a grounding bar, which shall be 3 feet long for the TC
and 10 feet long for the MC. Both shall be 4 inches wide by 1/4
inch thick with pre drilled NEMA bolt hole sizing and spacing.
This bar shall be attached to the main building grounding system
with a wire not smaller than #6 AWG copper. The ground wire shall
not share the cable tray with communications cabling. It may be
installed in a separate conduit, which may be attached to the
outside of the communications cabling cable tray.
Each distribution point shall be grounded to the main building ground,
NEC and EIA/TIA 607 requirement shall be followed.
- 2.2.5 LABELING
Communications, computer and
television conduit is to be clearly identified at every junction
box, via a painted section or by use of conduit stickers
indicating each conduit run:
- Green = computer and telephone
- Yellow = television
- Orange = fiber optic
All Telecommunication
Closet Frames, Main Cross-connect Frames and connecting blocks
must be properly identified by destination.
All riser
cables shall be properly marked with "from and to" indicators.
Marker is to be a flat piece of aluminum or wire tied plastic
labels. This marking shall be permanent and indicate:
- The Origination (Cable it is feeding from Main Cross-connect
Room #) to,
- The Destination (Telecommunications room# it is feeding).
All voice and data cable pairs in riser cables or
the entrance cable must be terminated on a connecting block and
identified.
2.3 CABLE
- 2.3.1 GENERAL
NOTE: ALL VOICE, DATA COAXIAL AND ANY COMMUNITION WIRING SHALL BE
PLELUM RATED IN ALL AREAS. The use of any PVC wiring used for
communication is Prohibited unless approved in writing from the
Telecommunication Center and must meet NFPA and NEC standards and codes.
A 50 percent growth factor
shall be built in for riser cable and provided for unless
otherwise specified; consequently any cable work that pertains to
telecommunications must be designed and/or approved by
Telecommunications Center. Project specifications will include
this growth factor.
All riser cables that extend from
the Main Cross-connect Room to each Telecommunication Closet must
be 100 percent terminated in the Main Cross-connect Room and in
each Telecommunication Closet.
Each telephone and data station cable shall have a minimum of 4
pairs; in some cases, a larger cable may be required. Telecommunications
Center will inform its designee or the contractor, via the project
specifications, in such cases.
To facilitate future cable installations, a new pull
string, tied off at both ends, shall be installed in conduit
simultaneously with the pull-in of cable.
All installed
station communication cables shall be minimum copper 4 pair, 24
AWG UTP, Category 6 (Enhanced), tested to 400 megahertz for voice
and data.
- 2.3.2 VOICE RISER CABLE
Voice riser cable
shall be copper, 24 AWG UTP, category 6. All station and riser
cable shall be run through and held in place with D-Rings in
telecommunications rooms and/or by use of wiretray. Terminate on
66 CAT5e connecting blocks. Block placement and management
backboards/relay rack location will be specified by
Telecommunications Center. Designation strips with cable counts
and jack ID shall be installed in all cases.
- 2.3.3 DATA RISER CABLE
All data riser cable will
be optical fiber cable, of either multi-mode and/or single-mode
type. In circumstances when optical fiber cable is not practical,
category 6, 24 AWG, 25 pair UTP cable shall be installed.
- 2.3.4 FIBER OPTIC RISER
Fiber optic riser cable shall consist of 12 strands of multi-mode
fiber and a second cable consisting of 6 strands of single mode fiber,
minimum. Termination in the MC and TC shall be on standard fiber patch
panels utilizing ST type connectors. Fiber riser shall be installed in
riser-rated inner-duct (3/4" I.D. min). or EMT multi -cell conduit.
2.4 RACKS AND PANELS
- 2.4.1 GENERAL
Each distribution point on the
telecommunication room backboard shall be identified as a building
entrance and/or a floor service panel. Junction/pull
boxes are to be provided on any conduit run longer than 80 feet.
All voice terminations at the MC will be on standard
raised 66 CAT5e connecting blocks, mounted on relay rack or
backboards. All data terminations at the TC will be terminated on
CAT 6 RJ45 jacks and inserted into QuickPort connecting panels
mounted on relay racks. Where space permits, freestanding racks
should be installed in the MC and the TC and all terminations
should be installed on the racks.
2.5 WIRE DRESS
- 2.5.1 VOICE STATION WIRES
Drop from the
telecommunication cable tray, bundle and route the unshielded
voice pair groups to the 66 CAT5e connecting blocks located on
the relay rack. Organize and label the cables in sequentially
numbered order.
- 2.5.2 DATA STATION WIRES
Drop from
telecommunications room cable tray, bundle and route to the data
patch panel located on the relay rack. Organize and label the
cables in serially numbered order.
2.6 VOICE/DATA RACK AND PATCH PANEL
To install network distribution panels and
associated equipment use the following installation method.
In TCs and MCs serving as a TC containing data
terminations, mount two free standing relay racks in the indicated
location. Position the racks to maintain a minimum of three (3)
feet clearance from the front of the rack to the front facing room
wall and three (3) feet clearance from the rear of the rack to the
rear facing room wall. If a row of racks is to be installed in a
telecommunications room, maintain a minimum of two (2) foot
clearance from the rightmost or leftmost rack to the opposing
wall. Anchor racks to the finished floor. Ground the rack to the
telecommunications room grounding busbar with #6 AWG copper wire.
Mount the voice network riser blocks in the left most
rack starting under the fiber interface unit if one is installed.
If no fiber interface unit is installed or to be installed in the
future, start at the top. Lay out the voice network blocks in
ascending serially numbered order from top left to bottom right.
When data jacks for multiple floors are serviced out of
the same TC or MC serving as a TC, the QuickPort panels shall be
laid out and labeled as follows:
- One or more 48 port horizontal panels will be dedicated
to each floor. Under no circumstances shall more than one floor
share a 48 port panel section. Panels will be installed with the
top most floor at the top of the rack and then in descending
order by floor.
- Additional racks may be required to satisfy this layout. If
so, the top most floor will be located in the left most rack
starting again from the top of the rack and then in descending
order.
- Panel labels shall match the jack labels as described in
Section 3.1.2. Each 48 port panel section shall be labeled with
the floor code letter.
- The right most rack is reserved for mounting network
electronics and support equipment.
- 2.6.1 PUNCH DOWN ON SURFACE MOUNTED BACKBOARDS
Lay down all station wire pairs in serially numbered
order from lowest serial number at the top left most position to
the highest serial number at the bottom right position.
Use 66 CAT5e connecting blocks. Route all cables to
be punched down to these blocks starting on the left most edge
down to the base of the backboard then over and up to the block
dressing the cable under the mounting legs. Fasten the mounting
brackets to the plywood backboard with #10 x 3/4 inch Phillips
head screws.
VOICE 4-Pair -- Use 66 CAT5e 100 pair
66 CAT5e blocks. Locate the punch blocks on the plywood wiring surface
in the area designated as Voice Station Wires. Set blocks in
top/down fashion and butt adjacent to each other when installing
left to right. Punch down the four (4) unshielded pairs on the
block. Minimum bend radius must meet the cable manufacturer's
specifications for category 6 wiring.
DATA 4-Pair --
Use rack mounted QuickPort patch panels. Punch down the four (4)
unshielded pairs on the RJ45 jack.
NOTE: The
blocks/panels for terminating the cable may be located on the
floor above or below the floor on which the station jack is
located. If this is the case, install panels in top/down fashion.
Minimum bend radius must meet the cable manufacturer's
specifications for category 6 wiring.
- 2.6.2 TERMINATIING AND CABLING STANDARDIZED PRODUCTS
Contact the Telecommunications Center for the equipment
required for all installations. Exceptions or substitutions must
be approved by Telecommunications Center.
|