| 
	 
			 Section 3 - COMMUNICATION OUTLETS - INSIDE 
            PLANT WIRING AND RACEWAYS 
             3.1 GENERAL 
             
              - 3.1.1 OVERVIEW 
 All telephone, data, video 
              station cabling shall be continuous cabling from the TC for voice, 
              data, video to the communication outlet. All station cables will 
              be free of kinks, chafes, and tight bends. Any ceiling tiles 
              removed by the contractor for cable installation will be 
              re-installed in good condition. Replacement of damaged tiles is 
              the contractor's responsibility at no cost to the university.
               The building occupant's present and future requirements 
              will determine the needs of multiple jack outlets. Final approval 
              for the layout of jacks shall rest with the Telecommunications 
              Center. During the programming stage Telecommunications Center, 
              consulting with the building occupant(s), will supply the jack 
              layout desired to the project architect for inclusion in the 
              project specifications.  
              All voice jacks shall terminate 
              in RJ-45 eight (8) conductor CAT 6 modular jack assemblies. The 
              voice jack shall be the top port(s) in the wall plate. If only one 
              voice jack, it should be terminated in the upper left port. Wire 
              color-coding shall be per EIA/TIA-568B specifications. 
               
              All data jacks shall terminate in RJ-45 eight (8) 
              conductor CAT 6 modular jack assemblies. The data jack shall be 
              the lower port(s) in the wall plate. If only one data jack, it 
              should be terminated in the lower left port. Wire color coding 
              shall be per EIA/TIA-568B specifications.  
              All pairs 
              shall be terminated on both voice and data jacks.  The 
              total wire path length from the data outlet to the 
              telecommunications room block must not exceed 295 feet (90 
              meters). This is important to meet Ethernet requirements of IEEE 
              802.3. Please note that in most cases the TC which houses network 
              electronics will service both the voice and data jacks on the 
              floor it is on. This must be considered when determining adherence 
              to the maximum length for the data outlet wiring. 
              
  
               - 3.1.2 LABELING 
 Each end of all cables will 
              be labeled at their termination locations.  
              All jack 
              modules shall be color coded to University of Mississippi 
              standards indicating that the top left jack is voice (blue) and 
              that the bottom left jack is data (red). The faceplate shall be 
              white.  
              Horizontal mounted jack positions shall be voice 
              on the left and data on the right.  Dual voice/data 
              jacks will utilize a single gang or double gang position face 
              plate with voice jacks in the top two positions, data jacks in the 
              bottom two positions and blank fillers in the spare positions. 
               All jacks shall be marked with identification numbers 
              as detailed below. 
			   Telecommunications Center will 
              provide the identification number range to be used for the 
              building(s). Upon project completion, the installing contractor or 
              designee of Telecommunications Center a list of jack 
              identification numbers used, their corresponding room numbers, 
              location within the room, and punch block or data panel 
              termination points. Jack identification numbers, at the jack 
              locations, shall also be placed on the as built drawings provided 
              by the contractor. 
              
  
               - 3.1.3 WIRING
 
			  Wiring for voice lines must be BLUE category 6 or greater as 
			  specified in the plans or specifications. Wiring for data circuits 
			  must be RED category 6 or greater as specified in the plans or 
			  specification. 
                
			  
			  
			  
			  
            3.2 COMMUNICATION OUTLET LOCATION 
             
              - 3.2.1 LOCATIONS AND QUANTITIES 
			  
 Unless 
              otherwise specified, a Standard Communications Outlet (SCO), shall 
              consist of a voice jack, a data jack, and two spare ports. Other 
              communication outlets may be installed depending on the function 
              for that particular office or room. 
              
                - Faculty Offices: Two (2) SCOs per designated occupant. 
                Outlets are to be installed on opposite walls. Any wall greater 
                than 15 ft. in length shall have outlets spaced evenly apart at 
                no more than 7 ft. intervals. Any wall greater than 15 ft. in 
                length shall have outlets spaced evenly apart at no more than 7 
                ft. intervals. 
                
 - Clerical/Staff Offices/Graduate Student Offices: One (1) SCO 
                at the location of each desk. 
                
 - Conference Rooms: One (1) SCO and one CATV outlet per room 
                for rooms up to 200 square feet. A minimum of four (4) SCOs and 
                two CATV outlets per room for rooms over 200 square feet. One 
                (1) SCO shall be located on each wall. CATV outlets will be 
                opposite from each other. Rooms with more than 500 square feet 
                shall have additional outlets equally spaced on each wall. CATV 
                outlet can be incorporated into a SCO spare port. 
                
 - Laboratories: One (1) SCO for each desk space. One ADA wall 
                mount height jack located inside laboratory near doorway for 
                wall mounted telephone. Additional outlet requirements will be 
                determined based on size and in the design phase of the project. 
                
 - Classrooms/Lecture Halls/Auditoriums: Classrooms with 
                teaching stations are required to have two (2) communication 
                jacks. One designated for data, one spare. A video cable shall 
                also be installed at the teaching station. Classrooms without a 
                teaching station shall use the following guidelines for video 
                cabling: 
                
                  - Number of Jacks: 1 Student Occupancy: 1-15 Student CATV 
                  Outlets: 1 
                  
 - Number of Jacks: 2 Student Occupancy: 15-50 Student CATV 
                  Outlets: 2 
                  
 - Number of Jacks: 4 Student Occupancy: 50-More Student CATV 
                  Outlets: 4 
    NOTE: * One TV outlet in the 
              front of room and another in the ceiling for projection TV. If the 
              classroom is designated as a High Tech Classroom, then the High 
              Tech Classroom requirements in Section 4. may supersede the CATV 
              outlet requirements listed above. 
              
                - Residence Hall Rooms: One (1) data communication jack per 
                occupant or potential occupant of each room. One (1) telephone 
                jack per room. One (1) CATV outlet per room. The locations will 
                be determined during design stages of the project. 
                
 - Residence Hall Lounges: One (1) or more communication jacks 
                and one (1) CATV outlet per lounge. The quantity and locations 
                will be determined during design stages of the project. 
                
 - Storage Areas: One (1) communication outlet per room. Two 
                (2) outlets for rooms over 500 square feet and one (1) 
                additional outlet for each additional 2000 square feet. 
                
 - Mechanical Rooms: Consult the Facilities Management. 
                
 - Some rooms require communications outlets for telephones or 
                energy management devices. 
                
 - Main Cross-connect Room and Telecommunication closets: One 
                (1) communication jack per room minimum. 
    
            3.3 COMMUNICATION OUTLET INSTALLATION 
             
              - 3.3.1 MOUNTING 
			  
 Use a dual gang outlet box 
              similar to Steel City, part number 72171-3/4 or Telecommunications 
              Center approved equivalent. When mounting the outlet box in a 
              steel studded wall, use a back brace. Use Steel City plaster 
              rings, part number 72-C13, (single gang) or 72-C-17 (double gang) 
              or the Telecommunications Center approved equivalent. It is 
              absolutely critical that the inside opening area match the outlet 
              installation enclosure. The plaster rings must be level and 
              positioned flush with the finished surface. For single voice/data 
              outlets use a single gang plaster ring. 
			   Outlets are to 
              be mounted at standard industry heights and positions, unless 
              otherwise specified by the Facilities Planning and/or 
              Telecommunications Center. Standard mounting height of 
              communication outlets: 
              
                - Desk 18 inches, AFF (above finished floor)(Single gang 
                plaster ring). 
                
 - Handicapped wall mount 48 inches, AFF (Single gang plaster 
                ring only). 
                
 - High Tech Classroom (See Section 4). 
                
 - CATV cable in classroom, auditorium, clinic lobby or lounge 
                is normally installed at the height of TV mounting. CATV cable 
                in offices, dorm rooms, or conference rooms is to be 
                incorporated into the communications outlet. 
  
				NOTE: 
              Electrical outlets shall be provided for TV and projection devices 
              by contractor.  
            3.4 COMMUNICATION JACKS 
             
              - 3.4.1 At each jack location Category 6 enhanced components 
              shall be installed. For each pair of cables, a Panduit 106 frame is 
              required. All conduit and makeup boxes at each workstation jack 
              shall be at least 2-1/8" deep. If installation is in a single gang 
              EMT or Makeup box, a Single Gang Faceplate is needed. If 
              installation is in a double gang box, a Double Gang Faceplate is 
              needed. 
              
 
               
               - 3.4.2 Panduit 106 Data Frame inserts shall be used in the 
              connector housing. Single inserts or dual inserts shall be used 
              for voice, and Category 6 enhanced inserts shall be used for data. 
              If no insert is required, a blank cover shall be installed. Part 
              numbers for the inserts are as follows: 
                
                - Red Category 6 Inserts Panduit CJ688TPRD 
                
 - Blue Category 6 Inserts Panduit CJ688TPBU 
                
 - Blank Inserts Panduit CMFBAxx 
                
 - F81 Splice Barrel Connector CMFBAxx 
  Note: xx is a 
              color designator to match the faceplate and 106 frames. 
              
  
               - 3.4.3 Voice (blue) is on the left; Data (red) is on the 
              right of the 106 frames.
  
			  
            3.5 WIRING PATHWAYS 
             
              - 3.5.1 GENERAL 
 To avoid electromagnetic 
              interference (EMI), all pathways should provide clearance of at 
              least: 
              
                - 4 feet (1.2 m) from motors or transformers 
                
 - 1 foot (0.3 m) from conduit and cables used for electrical 
                power distribution 
                
 - 5 in. (12 cm) from fluorescent lighting or power lines over 
                2kVA and up to 24 inches from any power line over 5kVA. 
              
  In general, communications cabling is routed 
              separately or several feet away from power cabling. Similarly, 
              communications cabling is routed away from large motors, 
              generators, induction heaters, arc welders, x-ray equipment, and 
              radio frequency, microwave or radar sources. Whenever possible, 
              pathways should cross perpendicular to fluorescent lighting and 
              electrical power cables or conduits.   
			  
            3.6 CONDUIT 
             
              - 3.6.1 GENERAL 
			  
 All conduit work shall meet 
              the requirements of the National Electrical Code. 
			   All voice, data and video wiring inside rooms shall be protected by 
              metallic conduit or other means such as wire mold or troughs in 
              the floor. Aluminum is not acceptable in caustic environments. 
              Plastic surface mount molding is not acceptable in any 
              application. EMT conduit or metal surface mount molding shall be 
              used for all interior wiring. All conduit is to be concealed 
              whenever possible. 
			   No more than an equivalent of two 
              (2) 90 degree bends are allowed in a run between junction boxes or 
              pull boxes. 
			   (LBs) are permitted. 
               Entrance to junction boxes or distribution panels shall 
              be adjacent to the corners or directly across from each other. 
               The use of plenum cable instead of conduit shall be 
              determined on a case by case basis. Telecommunications Center must 
              be contacted for approval. 
			   In major renovation and new 
              construction projects where the Main Cross-connect Room and 
              Telecommunication Closets are not in alignment, the contract shall 
              include provisions for installation of four (4) riser conduits (4 
              inches minimum diameter) from the MC to each TC. A pull string and 
              appropriate junction pull box shall also be provided in each 
              conduit run to facilitate future installation of cable(s). 
               To reduce EMI, all conduit in slab shall be a minimum 
              of 1 1/4 inches galvanized steel with threaded fittings. All 
              exceptions shall be determined during the design stage of the 
              project and shall be subject to the approval of Telecommunications 
              Center. 
			   All sleeves must protrude four (4) inches AFF 
              and below and be capped at both ends. Coordinate with 
              Telecommunications Center for the number of conduits entering the 
              facility. 
			   No horizontal conduit run shall be more than 
              80 feet between pull boxes. 
			   Conduit for telephone or 
              computer outlets shall be terminated in a dual gang box. Steel 
              City, part numbers 52151-1, 72151-1, 52-C-17 or 72-C-17 for one 
              (1) inch with dual gang plaster ring and 52151-3/4, 72151-3/4, 
              52-C-13 or 72-C-13, for 3/4 inch with single gang plastic ring. 
              Telecommunications Center approved equivalents to the Steel City 
              part numbers may be used. 
			   All communications outlets 
              shall be minimum 3/4 inch conduit, with a minimum of bends, from 
              the outlet to the cable tray, wire way or homerun directly to the 
              telecommunications room. Home run conduit is required when the 
              cable path above the ceiling is not easily accessible. Examples of 
              ceilings where conduit is required include dry wall and 
              interlocking ceiling tiles. Pull boxes must be installed every 180 
              degrees or 80 feet of the conduit run. See Section 4. for conduit 
              installation requirement for High Tech Classroom outlets. 
              
  
               - 3.6.2 CONDUIT CAPACITY 
			  
 Conduit shall be 
              sized using industry standard guidelines for telecommunications 
              distribution methods. Such guidelines can be found in the Building 
              Industry Consulting Service International (BICSI) 
              Telecommunications Distribution Methods Manual.   
			  
            3.7 LADDER/CABLE/WIRE TRAYS 
             
			   I. GENERAL MANUFACTURERS:
				Subject to compliance with requirements, provide products by 
				the following:
					
					  - A.	WBT, LLC.., 115 Harting Road, Centralia, IL 62801.  
						
 Phone: (618) 918-3821.  
						 Toll-Free:  (888) 492 8729.  
						 Fax: (618) 918 3825.  
						 Website:  www.wbtray.com  
						 Email: gary@wbtray.com  
					  - B.	[Approved Alternates: Select one of the following, 
					  if applicable.]
						
 1.	[Hoffmann]
						 2.	[Chatsworth]
						 3.	[Hubbell]
					   		
					 
				 II. MATERIALS AND FINISHES: 
						
					   A.	Cable Tray Materials: select one of the following: 
					  
							1.	[Carbon steel wire, ASTM A 510, Grade 1008.  
							Wire welded, bent, and surface treated after 
							manufacture.] 
							OR  
							 2.	[Carbon steel wire, ASTM A653, Continuous 
							galvanization before fabrication.]  Additional 
							finishing not required. 
					  B.	Cable Tray Finishes:
					  
					  1.	Finish for Carbon Steel Wire after welding and 
					  bending of mesh; select one of the following: 
						
						- a.	[Electrodeposited Zinc Plating:  ASTM B 633, 
						Type III, SC-1.]
 
						- b.	[Hot-Dip Galvanizing After Fabrication:  
						ASTM A 123.]
 
						- c.	[Powder-Coated:]
 
							1)	[Black powder-coated surface treatment. 
							2)	[Custom Color Powder-Coated surface treatment.  
					2.	Finish for Stainless Steel Wire: According to ASTM B 380.
					 
					 C.	Cable tray will consist of continuous, rigid, welded steel
					wire mesh cable management system, to allow continuous 
					ventilation of cables and maximum dissipation of heat, with UL 
					Classified splices where tray acts as Equipment Grounding 
					Conductor (EGC).  Wire mesh cable tray will have continuous 
					T-welded top wire to protect cable insulation and installers.  
					All cross wires to be WBT's SHAPE wire for maximum support.
					 
					D.	Provide splices, supports, and other fittings necessary 
					for a complete, continuously grounded system.  
					
					- 1.	Mesh:  2 x 4 inches (50 x 100 mm).
 
					- 2.	Straight Section Lengths:  118 inches (3,000 mm).
 
					- 3.	Wire Diameter:  5mm and 6mm as specified by manufacturer.  
 
					- 4.	Continuous T-Weld top wire to protect cable insulation and installers' hands.
 
					- 5.	Fittings: Wire mesh cable tray fittings are field-fabricated from straight 
					tray sections, in accordance with manufacturer's instructions and Item 2.3.
 
					- 6.	Cable Tray Size:
					
 
					
					a.	Depth:  Cable tray depth will be (unless otherwise shown on drawings):
						 1)	[2 inches]
						 2)	[4 inches]
						 3)	[6 inches]
						 4)	[8 inches] 
					 b.	Width:  Cable tray width will be (unless otherwise shown on drawings):
					 1)	2[ inches (50 mm)] 
						 2)	[4 inches (100 mm)] 
						 3)	[6 inches (150 mm)] 
						 4)	[8 inches (200 mm)] 
						 5)	[12 inches (300 mm)] 
						 6)	[18 inches (450 mm)] 						
						 7)	[20 inches (500 mm)]
						 8)	[24 inches (600 mm)] 					
					 c.	Length: Cable tray section length will be 118 inches 
					(3000mm) unless otherwise shown on drawings.
					 d.	Fill Ratio: Cable tray may be filled to 
					[40%] [50%] [60%] [100%] of total fill capacity.  
					Size cable tray to accommodate future cabling changes or additions.
						 
					   
					 					 
					 
              - 3.7.1 GENERAL  
			  
 All ladder trays shall be 
              designed to accommodate all types of communication cabling, 
              consequently any cable work that pertains to telecommunications 
              must be designed and/or approved by Telecommunications Center. 
               The minimum dimensions for a ladder tray shall be 12 
              inches wide and 4 inches deep. In certain instances, only when 
              indicated in the design specifications, a 6 inch wide by 3 inch 
              deep tray may be used.  Contract documents shall show 
              cross section of the communication wire way or cable tray. The 
              drawing must show reference to other utilities in the building. 
               All conduits terminating at a cable tray must be easily 
              accessible. Avoid ending conduits at tray in locations that are 
              not accessible by removable ceiling tile or ceiling access panel. 
              All conduits which are to be connected to the cable tray are to be 
              connected according to the manufacturer's specifications and must 
              meet the NEC.  Consideration may be given for 
              installation of other types of cables in a ladder tray to prevent 
              interference on unshielded cables. Location of such installation 
              shall be approved by Telecommunications Center.  Ladder 
              tray (cable tray) or wire way is to be supported with allthread 
              rods in a trapeze form. Supports for cable trays larger than 12 
              inches in width are to be installed according to the 
              manufacturer's specifications. Supports for cable trays 12 inches 
              or less may be farther apart but must meet the manufacturer's 
              installation requirements. A single support is not acceptable. All 
              supports are to be fastened to the building structure above. 
               Telecommunications Center or its designee will not 
              install any cable or perform any work until all installations are 
              made to comply with specifications. 
              
  
               - 3.7.2 MOUNTING 
 Cable trays must maintain a 
              minimum of six (6) inch clearance from obstructions above the tray 
              and a minimum of eight (8) feet AFF. Trays are to provide access 
              via the most direct path to all communications outlets on the 
              floor.  Install sweeping factory 90's for all turns. Use 
              end-of tray termination's where wire drops down to walls to 
              prevent abrasions and cuts from metal tray edges. Use a trapeze 
              cable tray mounting method suspended by manufacturer recommended 
              size allthread. Fasten allthread to ceiling anchors, allowing no 
              bends in allthread. Support the cable tray in this manner at every 
              section-to-section junction and at five (5) feet to six (6) feet 
              intervals (mid span) between joints. Whenever possible, the tray 
              should be no closer than six (6) inches from the structural 
              ceiling, ducts or pipes, considering all other possible 
              obstructions. A minimum of 5 inches distance from lighting, 
              especially fluorescent lighting, is required.   
            3.8 OPEN TOP CABLE SUPPORTS AND RINGS 
             
              - 3.8.1 GENERAL 
 3.8.1.1 All open top cable supports 
              (J-supports) and cable rings must be suspended from or attached to 
              the structural ceiling or walls with hardware or other 
              installation aids specifically designed to support their weight. 
              When used, J-supports or cable rings shall be located on 48 to 60 
              inch centers to adequately support and distribute the cables 
              weight. These types of supports may typically hold up to fifty 
              0.25 inch diameter cables. 3.8.1.2 For larger quantities of 
              cables that convene at the Telecommunication Closets, provide 
              cable trays or other special supports that are specifically 
              designed to support the required cable weight and volume. 
               3.8.1.3 Hooks and straps shall be attached to building members 
              with fasteners appropriate for the material. Wood screws or lag 
              bolts shall be used for wood, wood screws with plastic anchors 
              shall be used for plaster and concrete, and self-taping screws 
              shall be used for sheet metal. Threaded metal hooks attached to 
              threaded anchors are also acceptable.  3.8.1.4 Unistrut may be 
              used where necessary to support large bundles of cables or to 
              provide attachment points for EMT, metal Makeup, or Panduit 
              raceway. Unistrut allthread hangers shall be mounted with threaded 
              anchors.  3.8.1.5 Large hooks that will carry the weight of 
              many cables shall be attached with lag bolts, metal concrete 
              anchors, or metal anchors with epoxy. The anchors shall extend 
              into the mounting material at least 3 inches.  3.8.1.6 Straps 
              and hooks shall be oversized so that additional cables can easily 
              be installed in the future. Hooks and straps shall be filled to no 
              more than 75% of the capacity.  3.8.1.7 Hooks or straps shall 
              be mounted no more than four feet apart. Closer spacing may be 
              necessary in areas where cables are routed around corners or are 
              in close proximity to other mechanical electrical systems. 
               3.8.1.8 In special cases where the area above lay-in ceilings 
              has obstructions and attaching straps to the ceiling is difficult 
              or impossible, straps can be attached to metal clips mounted on 
              wire hangers that hold up the ceiling grid.  3.8.1.9 When 
              cables are installed in the wall no box is required, but a 
              mounting bracket shall be mounted securely in the wall. 
               3.8.1.10 All conduit and makeup boxes at each workstation jack 
              shall be at least 2-1/8" deep. This depth is required to 
              accommodate the Category 6 enhanced (CAT6) jack. When a box is used as 
              both a jack and pull box, the minimum box depth shall be 3-1/8". 
              If fiber is installed in the box an Ortronix extender plate is to 
              be used. 
               3.8.1.11 In instances where EMT (metal conduit) is 
              used, all empty conduits shall contain a pull string. A pull box, 
              splice box, or pulling point containing pull strings in each 
              direction shall be installed for any constrained pathway where 
              there are more than two 90 degree bends, a 180 degree reverse bend 
              or length greater than 100 feet.  3.8.1.12 Cable in exposed 
              finished areas shall be installed in raceway such as EMT conduit, 
              metal Makeup, or Panduit.    
            3.9 UNDERFLOOR DUCT SYSTEM 
             
              - 3.9.1 GENERAL 
 This type of raceway is to be 
              used minimally at all costs. Care must be taken to design a system 
              that will consider electrical and communications requirements. 
              Adequate electricity must be available at all locations. With 
              proper planning, an adequate system can be installed but it is 
              discouraged.   
			  
			    |